Circuit breaker closing time measurement, “From Pos to Pos”
“From Pos to Pos” measures the closing time from auxiliary contacts. This will not
represent the actual closing time but it can be used to check that circuit breaker
reaches end state and that it will not hang to intermediate state (POSOPN and POS
CLS are both False).
This mode is recommended only for supervision purposes to alarm
incase breaker doesn’t close properly, not to measure actual travelling
time .
Circuit breaker closing time measurement, “From Cmd to Curr”
“From Cmd to Curr” measures the closing time from binary output activation till
current is flowing in the primary circuit. This operation mode requires that current
signal is connected to I3P1 and I3P2 inputs.
POSOPN_CB2 – AUX BIN
POSCLS_CB2 – AUX BIN
Current in Feeder 2 /
CB2
OPEN_CB2 – FB CMD
CLOSE_CB2 – FB CMD
RELAY BINARY OUTPUT
Closing �me
1 2
3
Internal Logic + BO ac�va�on delay
Figure 950: Circuit breaker closing time measurement (“From Cmd to Curr”)
1
HSABTC function activates
CLOSE_CB2
output
2
Relay binary output activates – closing time measurement starts from this
point
3
Circuit breaker main contacts close and current flows
Recommended operation mode
Control functions
1MRS759142 F
1784
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......