Table 720: MPDIF Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Slope section 3
10...100
%
1
100
Slope of the third
line of the operat-
ing characteristics
DC restrain enable
0=False
1=True
0=False
Setting for ena-
bling DC restrain
feature
Table 721: MPDIF Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
CT connection type 1=Type 1
2=Type 2
1=Type 1
CT connection
type. Determined
by the directions of
the connected cur-
rent transformers
CT ratio Cor Line
0.40...4.00
0.01
1.00
CT ratio correction,
line side
CT ratio Cor Neut
0.40...4.00
0.01
1.00
CT ratio correction,
neutral side
4.3.7.9
MPDIF Monitored data
Table 722: MPDIF Monitored data
Name
Type
Values (Range)
Unit
Description
OPR_A
BOOLEAN
0=False
1=True
Operate phase A
OPR_B
BOOLEAN
0=False
1=True
Operate phase B
OPR_C
BOOLEAN
0=False
1=True
Operate phase C
INT_BLKD_A
BOOLEAN
0=False
1=True
Internal block status
phase A
INT_BLKD_B
BOOLEAN
0=False
1=True
Internal block status
phase B
INT_BLKD_C
BOOLEAN
0=False
1=True
Internal block status
phase C
ID_A
FLOAT32
0.00...80.00
xIr
Differential current
phase A
ID_B
FLOAT32
0.00...80.00
xIr
Differential current
phase B
ID_C
FLOAT32
0.00...80.00
xIr
Differential current
phase C
IB_A
FLOAT32
0.00...80.00
xIr
Biasing current phase A
IB_B
FLOAT32
0.00...80.00
xIr
Biasing current phase B
IB_C
FLOAT32
0.00...80.00
xIr
Biasing current phase C
I_ANGL_A1_B1
FLOAT32
-180.00...180.00
deg
Current phase angle
phase A to B, line side
I_ANGL_B1_C1
FLOAT32
-180.00...180.00
deg
Current phase angle
phase B to C, line side
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
803
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......