
are the same or greater than
Activation day and Activation month settings, output
Q
is activated and remains active till the date reaches the set
Deactivation day and
Deactivation month settings.
Activation of the
BLOCK
input deactivates the function output whereas the
activation of the
FREEZE
input freezes the output. The
BLOCK
input always has a
higher priority than the
FREEZE
input.
The module automatically handles the leap day and different month lengths.
• The function output remains active during the leap day if the leap day falls within
the set activation period.
• If the set
Activation day is not a valid date (for example, 31st April), then the
output does not activate.
• If the set
Deactivation day is not a valid date (for example, 31st April), then the
last date of the month is considered.
Q
5/12
10/12
20/12
15/12
31/12
25/12
Set
Activation day
= 07,
Activation month
= December
Set
Deactivation day
= 22,
Deactivation month
= December
7/12
22/12
Q
20/12
25/12
5/1
31/12
15/1
10/1
Set
Activation day
= 22,
Activation month
= December
Set
Deactivation
day = 07,
Deactivation
month = January
22/12
7/1
Figure 133: Examples of how output Q is activated for different settings
3.20.4.5
Application
The function activates an output for a specific set duration of the calendar year.
Consider an application where the output of the daily timer function DTMGAPC
needs to be activated only for specific days of the calendar year. The output of
CALGAPC can be connected to the
BLOCK
input of DTMGAPC (using NOT gate) so
that DTMGAPC activates only for the duration defined by CALGAPC.
Figure 134: Example of Calendar function usage
3.20.4.6
Signals
Basic functions
1MRS759142 F
242
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......