Parameter
Values (Range)
Unit
Step
Default
Description
Start value df/dt
-0.2000...0.2000
xFn/s
0.0001
0.0100
Frequency start val-
ue rate of change
Operate Tm Freq
80...5400000
ms
10
200
Operate delay time
for frequency
Operate Tm df/dt
120...200000
ms
10
400
Operate delay time
for frequency rate
of change
Table 886: FRPFRQ Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 887: FRPFRQ Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay Tm
Freq
0...60000
ms
1
0
Reset delay time
for frequency
Reset delay Tm
df/dt
0...60000
ms
1
0
Reset delay time
for rate of change
4.6.1.9
FRPFRQ Monitored data
Table 888: FRPFRQ Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Start duration
ST_DUR_OFRQ
FLOAT32
0.00...100.00
%
Start duration
ST_DUR_UFRQ
FLOAT32
0.00...100.00
%
Start duration
ST_DUR_FRG
FLOAT32
0.00...100.00
%
Start duration
FRPFRQ
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.6.1.10
Technical data
Table 889: FRPFRQ Technical data
Characteristic
Value
Operation accuracy
f>/f<
±5 mHz
df/dt
±50 mHz/s (in range |df/dt|
<5 Hz/s)
±2.0% of the set value (in
range 5 Hz/s <
|df/dt| < 15 Hz/s)
Start time
f>/f<
<80 ms
1
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
927
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......