Parameter
Values (Range)
Unit
Step
Default
Description
2=Leading
Start reset Val Dir
1=Lagging
2=Leading
1=Lagging
PF direction for
start reset value
Alarm value Dir
1=Lagging
2=Leading
1=Lagging
PF direction for
alarm value
Alarm reset Val Dir
1=Lagging
2=Leading
1=Lagging
PF direction for
alarm reset value
Start value
-0.99...0.99
0.01
0.80
Start value
Start reset value
-0.99...0.99
0.01
0.85
Value at which start
resets, drops out
Alarm value
-0.99...0.99
0.01
0.85
Alarm start value
Alarm reset value
-0.99...0.99
0.01
0.90
Value at which
alarm resets, drops
out
Operate delay time 100...300000
ms
1
500
Time delay for op-
eration
Alarm delay time
100...300000
ms
1
500
Time delay for
alarm
Table 1023: MPUPF Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Min operate current 0.05...0.65
xIn
0.01
0.10
Minimum operating
current
Min operate volt-
age
0.05...0.50
xUn
0.01
0.10
Minimum operating
voltage
Disable time
0...60000
ms
1
5000
Additional wait
time after CB clos-
ing
Voltage reversal
0=No
1=Yes
0=No
Rotates the PF by
180 degrees
Table 1024: MPUPF Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
4.8.4.9
MPUPF Monitored data
Table 1025: MPUPF Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
PF
FLOAT32
-1.00...1.00
Calculated value of the
3-phase power factor
MPUPF
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Protection functions
1MRS759142 F
1084
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......