The measured system frequency is compared to the set value to detect the
underfrequency condition. The measured rate of change of frequency (df/dt)
is compared to the set value to detect a high frequency reduction rate. The
combination of the detected underfrequency and the high df/dt is used for
the activation of the load-shedding. There is a definite time delay between the
detection of the underfrequency and high df/dt and the activation of LSHDPFRQ.
This time delay can be set and it is used to prevent unwanted load-shedding actions
when the system frequency recovers to the normal level.
Throughout this document, “high df/dt” is used to mean “a high rate of
change of the frequency in negative direction.”
Once the frequency has stabilized, LSHDPFRQ can restore the load that is
shed during the frequency disturbance. The restoration is possible manually or
automatically.
The function contains a blocking functionality. It is possible to block function
outputs, timers or the function itself.
4.6.2.4
Analog channel configuration
LSHDPFRQ has one analog group input which must be properly configured.
Table 891: Analog inputs
Input
Description
U3P
Three-phase voltages
See the preprocessing function blocks in this document for the possible
signal sources.
There are a few special conditions which must be noted with the configuration.
Table 892: Special conditions
Condition
Description
U3P connected to real measurements
The function requires that at least one phase
or phase-to-phase voltage channel is connec-
ted.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.6.2.5
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of LSHDPFRQ can be described using a module diagram. All the
modules are explained in the next sections.
1MRS759142 F
Protection functions
REX640
Technical Manual
929
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......