ILTCTR Output signals
Table 119: ILTCTR Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm
WARNING
BOOLEAN
Warning
I3P
SIGNAL
Three-phase currents
IRES_CLC
SIGNAL
Residual current, calculated
IRES_CLC_DR
SIGNAL
Residual current, calculated,
for disturbance recorder
IL1_DR
SIGNAL
Phase current IL1 for disturb-
ance recorder
IL2_DR
SIGNAL
Phase current IL2 for disturb-
ance recorder
IL3_DR
SIGNAL
Phase current IL3 for disturb-
ance recorder
NPS_DR
SIGNAL
Negative sequence current
for disturbance recorder
PPS_DR
SIGNAL
Positive sequence current for
disturbance recorder
3.17.1.5
Settings
ILTCTR Settings
Table 120: ILTCTR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Current input type
2=Current trafo
4=Current sensor
2=Current trafo
Type of the current
input
Primary current
1.0...15000.0
A
0.1
100.0
Rated primary cur-
rent
Secondary current
2=1A
3=5A
2=1A
Rated secondary
current
Rated secondary
Val
1.000...150.000
mV/Hz
0.001
3.000
Rated Secondary
Value (RSV) ratio
Amplitude Corr A
0.9000...1.1000
0.0001
1.0000
Phase A amplitude
correction factor
Amplitude Corr B
0.9000...1.1000
0.0001
1.0000
Phase B amplitude
correction factor
Amplitude Corr C
0.9000...1.1000
0.0001
1.0000
Phase C amplitude
correction factor
Angle Corr A
-8.0000...8.0000
deg
0.0001
0.0000
Phase A angle cor-
rection factor
Angle Corr B
-8.0000...8.0000
deg
0.0001
0.0000
Phase B angle cor-
rection factor
Angle Corr C
-8.0000...8.0000
deg
0.0001
0.0000
Phase C angle cor-
rection factor
1MRS759142 F
Basic functions
REX640
Technical Manual
193
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......