
Equivalent load Dis
U
U
d real
d tap d
=
=
(
)
(
,
)
1
(Equation 297)
U
d(real)
The actual maximum voltage drop of the feeder
U
d(tap,d=1)
The fictional voltage drop, if the entire load would be tapped at the end (d=1)
of the feeder (not drawn in
). The calculation of this value requires
data from the DMS system.
Alternatively, the setting
Equivalent load Dis can be determined by conducting a
single-phase earth-fault test (R
fault
= 0 Ω) at that point of the feeder where the
maximum actual voltage drop takes place. This point is typically located at the end
of the main line. As a result, the calculated value is stored in the recorded data
Equivalent load Dis.
In addition, when the setting
EF algorithm Sel is equal to "Load modelling", the
EF algorithm Cur Sel setting determines whether the used algorithm is based on
zero-sequence "Io based" or negative-sequence "I2 based" current. The difference
between "Io based" and "I2 based" methods is that "I2 based" does not require the
Ph capacitive React and Ph leakage Ris settings. In case of "Io based", these settings
are needed to compensate for the influence of the line-charging capacitances of the
protected feeder. This improves the accuracy of the fault location estimate when
fault resistance is involved in the fault.
With certain restrictions, the “Load modelling” algorithm can also be applied to
unearthed networks. In this case the
EF algorithm Cur Sel setting should be set
to “Io based” and thus
Ph capacitive React and Ph leakage Ris settings must be
determined.
The prerequisite for the operation of SCEFRFLO in earth faults in unearthed
networks is that the earth-fault current of the network corresponding to a solid
fault exceeds the pre-fault load current; that is the
is valid.
Flt to Lod Cur ratio
I
I
ef Rfault
Load
=
≥
=
(
)
0
1
(Equation 298)
This ratio is estimated by SCEFRFLO and stored in the recorded data Flt to Lod Cur
ratio together with the fault distance estimate.
In case of an unearthed network, sufficient fault current magnitude resulting in Flt
to Lod Cur ratio >1 can be achieved, for example, with proper switching operations
in the background network, if possible, which increase the fault current. If the faulty
feeder is re-energized after the switching operation, a new estimate for the fault
distance can be obtained. Fault resistance decreases the fault location accuracy
so the resistance should not be higher than a few hundred ohms. Also, a low
value of Flt to Lod Cur ratio causes inaccuracy and affects the quality of the fault
distance estimate. The inaccuracies affecting the calculated fault distance estimate
are reported in the recorded result quality indicator value Flt Dist quality in
Protection related functions
1MRS759142 F
1200
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......