of radial feeders, this algorithm can be applied with low-impedance/effectively
earthed systems where the fault current is fed from one side only. The “Load
modelling” algorithm has been especially designed for unearthed systems.
The “Load modelling” algorithm requires the
Equivalent load Dis setting, that is, an
equivalent load distance, as an additional parameter. The derivation and meaning of
this parameter is illustrated in
, where the load is assumed to be evenly
distributed along the feeder, resulting in the actual voltage drop curve as seen in the
middle part of
In case of evenly distributed load,
Equivalent load Dis ~ 0.5. When the load is
tapped at the end of the feeder,
Equivalent load Dis = 1.0. If the load distribution
is unknown, a default value of 0.5 can be used for
Equivalent load Dis.
The maximum value of the voltage drop, denoted as U
drop
(real), appears at the end
of the feeder. The
Equivalent load Dis setting is the distance at which a single load
tap corresponding to the total load of the feeder results in a voltage drop equal to
U
drop
(real). The dashed curve shows the voltage drop profile in this case.
Figure 684: Description of the equivalent load distance
The exact value for
Equivalent load Dis can be calculated based on the load flow and
voltage drop calculations using data from DMS-system and the following equation.
1MRS759142 F
Protection related functions
REX640
Technical Manual
1199
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......