Power quality in the voltage waveform is evaluated by measuring voltage swells,
dips and interruptions. PHQVVR includes single-phase and three-phase voltage
variation modes.
Typically, short-duration voltage variations are defined to last more than half of the
nominal frequency period and less than one minute. The maximum magnitude (in
the case of a voltage swell) or depth (in the case of a voltage dip or interruption)
and the duration of the variation can be obtained by measuring the RMS value of
the voltage for each phase. International standard 61000-4-30 defines the voltage
variation to be implemented using the RMS value of the voltage. IEEE standard
1159-1995 provides recommendations for monitoring the electric power quality of
the single-phase and polyphase ac power systems.
PHQVVR contains a blocking functionality. It is possible to block a set of function
outputs or the function itself.
10.3.4
Analog channel configuration
PHQVVR has two analog group inputs which must be properly configured.
Table 1630: Analog inputs
Input
Description
I3P
1
Three-phase currents
U3P
Three-phase voltages
See the preprocessing function blocks in this document for the possible
signal sources. The
GRPOFF
signal is available in the function block called
Protection.
There are a few special conditions which must be noted with the configuration.
Table 1631: Special conditions
Condition
Description
U3P connected to real meas-
urements
The function can work with one voltage channel connected
(A, B or C depending on the
Phase supervision
setting "Ph A",
"Ph B" or "Ph C") if
Phase mode
is set to "Single Phase".
The function can work with two voltage channel connected
(A-B, B-C or C-A depending on the
Phase supervision
setting
"Ph A+B", "Ph B+C" or "Ph A+C") if
Phase mode
is set to
"Three Phase".
The function requires that all three voltage channels are con-
nected if
Phase supervision
is set to "Ph A+B+C" and
Phase
mode
setting is set to "Three Phase".
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
1
Can be connected to
GRPOFF
Power quality measurement functions
1MRS759142 F
1830
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......