counter threshold voltage and Input counter threshold hysteresis settings. Oxide-
burn feature cannot be disabled in BIO1002 & BIO1004.
In RTD1002 module wetting current can be adjusted by setting the parameter
Input oxide burn A in Configuration > I/O modules > Slot # > Input filtering. This
parameter is common for all binary inputs in the module.
3.13.1
Binary input threshold voltage
The parameter
Input threshold voltage is used to set the threshold level of the
binary inputs.
Input threshold voltage determines the voltage level for the activation
of the inputs. The threshold can be set for every module or slot specifically
depending on the
Slot specific threshold setting.
Table 95: Input threshold voltage parameters
Parameter
Values
Default
Slot specific threshold
0=False
1=True
0=False
Input threshold voltage
16…176 V
16 V
3.13.2
Threshold hysteresis
Threshold hysteresis is used to determine the deactivation threshold for the binary
inputs in case of voltage drops in the auxiliary voltage supply. Threshold hysteresis
value determines how low the deactivation voltage is compared to the activation
voltage as a percentage. Hysteresis can be set for every module or slot specifically
depending on the
Slot specific hysteresis setting.
Binary inputs always deactivate when the voltage level drops below 14 V.
Table 96: Threshold hysteresis parameters
Parameter
Values
Default
Slot specific hysteresis
0=False
1=True
0=False
Input threshold hysteresis
10…50 %
10 %
3.13.3
Binary input filter time
The filter time eliminates debounces and short disturbances on a binary input. The
filter time is set for each binary input of the protection relay.
1MRS759142 F
Basic functions
REX640
Technical Manual
161
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......