Using power output contacts without trip circuit supervision
In case of mechanical outputs, if TCS is not used, the internal current drain
(PSM100x.X2:4, PSM100x.X2:9 and PSM100x.X2:14 in PODP1, PODP2 and PODP2
outputs, respectively) can be left unconnected. The output can then be used as a
normal power output.
Incorrect connections and use of trip circuit supervision
Although the TCS circuit in the PODP1, PODP2 and PODP2 outputs consists of two
separate contacts, it must be noted that those are designed to be used as series
connected to guarantee the breaking capacity given in the technical manual of the
protection relay.
shows incorrect usage of a TCS circuit when only one of
the contacts is used.
(+)
(-)
Relay
R
ext
R
ext
R
int
R
int
TCS
TCS
(+)
(-)
Relay
R
ext
R
ext
R
int
R
int
TCS
TCS
Trip
coil
CB operating
mechanism
CB operating
mechanism
Trip
coil
Figure 743: Incorrect connection of trip-circuit supervision
6.1.6
Signals
6.1.6.1
TCSSCBR Input signals
Table 1239: TCSSCBR Input signals
Name
Type
Default
Description
TCS_STATE
BOOLEAN
0=False
Trip circuit supervi-
sion status
BLOCK
BOOLEAN
0=False
Block input status
6.1.6.2
TCSSCBR Output signals
Table 1240: TCSSCBR Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm output
1MRS759142 F
Supervision functions
REX640
Technical Manual
1309
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......