Timer 1
Once activated, the Timer 1 module activates the
ST_OVLOD
output. The operation
time depends on the overload level and
Time multiplier. The operation time
under standard characteristics is based on ANSI/IEEE 37.99 and IEC 60871-1
recommendations.
Table 1054: Standard Curve characteristics for IDMT Curve
Overload value
IED operate time(s) with k =
1
Standard
1.10
43200
IEC60871-1
1.15
1800
IEC60871-1
1.20
300
IEC60871-1
1.30
60
ANSI/IEEE37.99,IEC60871-1
1.40
15
ANSI/IEEE37.99
1.70
1
ANSI/IEEE37.99
2.20
0.120
ANSI/IEEE37.99
Operate time is based on maximum value of I_PEAK_INT_A, I_PEAK_INT_B and
I_PEAK_INT_C. From maximum value calculated , operate time between any two
consecutive points in the standard table is based on logarithmic interpolation.
The operate time can be scaled using the
Time multiplier setting. The
OPR_OVLOD
output is activated if the overload situation lasts long enough to exceed the
operation time.
The operate time for the operation overload stage is limited between 0.1
s to 43200 s (12 hours) if
Time multiplier is used.
Protection functions
1MRS759142 F
1112
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......