Fault indication
Fault
code
Additional
information
Fast self-
recovery
attempt
Slow 10min
self-
recovery
(# of
attempts)
Immediate
IRF-mode
Action in permanent fault
state
Internal Fault
EEPROM error
82
Start up error: Er-
ror in the EEPROM
memory on the
CPU module.
No
No
Yes
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
ing, replace the relay, most
probably hardware failure
in CPU module.
Internal Fault
EEPROM error
82
Start up error: CRC
check failure in the
EEPROM memory
on boot-up on the
CPU module.
Yes
Yes (3)
No
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
ing, replace the relay, most
probably hardware failure
in CPU module.
Internal Fault
FPGA error
83
Runtime error: Er-
ror in the FPGA on
the CPU module.
Yes
Yes (3)
No
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
ing, replace the relay, most
probably hardware failure
in CPU module.
Internal Fault
RTC error
84
Start up error: Er-
ror in the RTC on
the CPU module.
Yes
No
Yes
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
ing, replace the relay, most
probably hardware failure
in CPU module.
Internal Fault
COM card error
116
Runtime error: Er-
ror in the COM
card.
Yes
Yes (3)
No
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restarting,
exchange the communica-
tion module in slot X000.
Internal Fault
SO-relay(s), Slot
C
-10
Runtime error:
Faulty Signal Out-
put relay(s) in card
located in slot C.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot C.
Internal Fault
SO-relay(s), Slot
E
-11
Runtime error:
Faulty Signal Out-
put relay(s) in card
located in slot E.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot E.
Internal Fault
SO-relay(s), Slot
A2
-12
Runtime error:
Faulty Signal Out-
put relay(s) in card
located in slot A2.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot A2.
Internal Fault
SO-relay(s), Slot
B
-13
Runtime error:
Faulty Signal Out-
put relay(s) in card
located in slot B.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot B.
Table continues on the next page
1MRS759142 F
Basic functions
REX640
Technical Manual
103
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......