Figure 383: Influence of the tapped transformer load current to the stabilized low
stage setting
The stabilized stage provides both DT and IDMT characteristics that are used for
time selective protection against faults which are not covered by the instantaneous
stage. The impedance of the line is typically an order of magnitude lower than the
transformer impedance providing significantly higher fault currents when the fault
is located on the line.
Z=10%
33kV
A
kV
kVA
I
F
23
.
96
10
.
0
33
3
500
1
.
1
400A/1
400A/1
500kVA
In
st
.
Ti
me
de
lay
e
d
%
24
24
.
0
1A
*
400
23
.
96
I
A
A
A
RED 615
RED 615
Figure 384: Influence of the short circuit current at LV side of the tapped
transformer to the differential current
Detection of the inrush current during transformer start-up
When the line is energized, the transformer magnetization inrush current is seen as
differential current by the line differential protection and may cause malfunction of
the protection if not taken into account. The inrush situation may only be detected
on one end but the differential current is always seen on both ends. The inrush
Protection functions
1MRS759142 F
674
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......