CL_COMMAND or
Synchronize CB
SYNC_INPRO
SYNC_OK
CLOSE_CB
t =
Maximum Syn time
Figure 874: Determination of closing signal CLOSE_CB when Multiple command is
set to "Off"
CL_COMMAND or
Synchronize CB
SYNC_INPRO
SYNC_OK
CLOSE_CB
t =
Maximum Syn time
Figure 875: Determination of closing signal CLOSE_CB when Multiple command is
set to "On"
The
SYNC_INPRO
output is active when the close command (
CL_COMMAND
or
Synchronize CB) is in progress and it is reset when the close command is reset
or
Maximum Syn time has elapsed. In this automatic mode the closing signal
CLOSE_CB
is activated automatically once all the closing conditions are satisfied.
If the closing conditions are fulfilled during a permitted check time set with
Maximum Syn time, ASNSCSYN gives synchro check permission to the circuit-
breaker control CBXCBR after the closing command signal is delivered. The
simplified configuration block diagram of ASNSCSYN with
CLOSE_CB
to CBXCBR
is shown in
1MRS759142 F
Control functions
REX640
Technical Manual
1597
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......