I
ASNSCSYN
CBXCBR
CLOSE_CB
AU_CLOSE EXE_CL
SYNC_OK
SYNC_OK
Figure 876: Simplified configuration block diagram of ASNSCSYN in auto
synchronization mode operation
Alarms generation
In auto synchronization control mode, the closing command generation is activated
either by the command input
CL_COMMAND
or by command parameter
Synchronize
CB.
After the closing command activation, if the conditions for closing CB are not
fulfilled within the set time of
Maximum Syn time, a failed closing attempt alarm
is given. The
CL_FAIL_AL
alarm output signal is pulse-shaped and the pulse length
is 500 ms.
CLOSE_CB
t =
Maximum Syn time
CL_FAIL_AL
t = 500 ms
CL_COMMAND or
Synchronize CB
Figure 877: Determination of checking time for closing
CB closing is permitted during
Maximum Syn time, starting from the moment
the close command is activated. The close command must be active while the
closing conditions are fulfilled, otherwise the procedure is cancelled. If the closing
conditions are fulfilled during
Maximum Syn time, a closing pulse output is delivered
to the CB. If the closing conditions are not fulfilled during the checking time, the
alarm
CL_FAIL_AL
is activated as an indication of a failed closing attempt. The
closing pulse is not delivered if the closing conditions become valid after
Maximum
Syn time has elapsed. The closing pulse is delivered only once for each activated
close command, and a new closing command sequence cannot be started until the
close command is reset and reactivated.
CBXCBR receives information about the CB status and thus is able to adjust
the command signal to be delivered to ASNSCSYN. If the closing command is
Control functions
1MRS759142 F
1598
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......