Ph capacitive React
U
I
xy
ef
=
⋅
3
(Equation 311)
U
xy
Phase-to-earth voltage
SCEFRFLO can also determine the value for the
Ph capacitive React setting by
measurements. The calculation of
Ph capacitive React is triggered by the binary
signal connected to the
TRIGG_XC0F
input when an earth-fault test is conducted
outside the protected feeder during commissioning, for example, at the substation
busbar. The
Calculation Trg mode has to be “External”. After the activation of the
TRIGG_XC0F
triggering input, the calculated value for setting
Ph capacitive React
is obtained from recorded data as parameter
XC0F Calc. This value has to be
manually entered for the
Ph capacitive React setting. The calculated value matches
the current switching state of the feeder so if the switching state of the protected
feeder changes, the value should be updated.
shows an example configuration, which enables the measurement of
setting
Ph capacitive React.
Figure 691: An example configuration, which enables the measurement of setting Ph capacitive React
If the earth fault is detected by the residual overvoltage function (
START
of
ROVPTOV), but not seen by the forward-looking earth-fault protection function
(
START
of DEFLPDEF), the fault is located outside the protected feeder. This
is mandatory for valid measurement of setting
Ph capacitive React. After a set
delay (TONGAPC), the input
TRIGG_XC0F
is activated and the parameter
XC0F Calc
in the recorded data is updated. The delay (TONGAPC) must be set longer than
the start delay of the directional earth-fault function DEFLPDEF, but shorter than
the minimum operating time of the directional earth-fault functions in any of the
feeders. For example, if the start delay is 100 ms and the shortest operating time
300 ms, a value of 300 ms can be used. Circuit breaker and disconnector status is
used to verify that the entire feeder is measured.
Modeling a non-homogeneous line
A typical distribution feeder is built with several different types of overhead lines
and cables. This means that the feeder is electrically non-homogeneous. SCEFRFLO
allows the modeling of the line impedance variation in protection relay with three
line sections with independent impedance settings. This improves the accuracy of
1MRS759142 F
Protection related functions
REX640
Technical Manual
1211
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......