Table 1476: Position indication values based on switch type
Status
Switch type
POSITION
Three-position
switch
Disconnector
Earthing switch
Earthing switch
closed
Earthing switch
closed and discon-
nector open
N/A
Earthing switch
closed
Earthing switch inter-
mediate
Earthing switch inter-
mediate and discon-
nector open
N/A
Earthing switch inter-
mediate
Both open
Earthing switch open
and disconnector
open
Disconnector open
Earthing switch open
Disconnector inter-
mediate
Earthing switch open
and disconnector in-
termediate
Disconnector inter-
mediate
N/A
Disconnector closed
Earthing switch open
and disconnector
closed
Disconnector closed
N/A
Faulty
Earthing switch faulty
or disconnector faul-
ty (or incorrect com-
bination)
Faulty
Faulty
When controlling P3SXSWI with RIO600 SCM, the switch's position
information should be made available to the function in the protection
relay via GOOSE or binary inputs from RIO600 to reflect correct position
and status information.
9.2.4.2
Control of a three-position switch
There are three possible end positions in a three-position switch: earthing switch
closed, both open, and disconnector closed. Additionally, there are two intermediate
states: earthing switch intermediate and disconnector intermediate. The function
follows the command order in cyclic order as shown in
. For example,
at disconnector close state only disconnector open command can be executed.
Similarly, when the state is both open, both disconnector close and earth close
commands can be executed. When the switch indicates earthing switch or
disconnector intermediate position (for example, the motor has stopped due to
timeout), a specified open command is allowed only.
1MRS759142 F
Control functions
REX640
Technical Manual
1523
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......