Residual voltage transfer
The residual voltage transfer is utilized when a connection in the 1
st
phase
coincidence is not possible. Following conditions must be met for residual voltage
transfer:
• transfer is running
• both breakers are open
• DISA_RES is FALSE
• setting
Ena Res V transfer allows transfer
• if transfer is initiated manually, then ENA_FASTONLY must be FALSE
The connection of the stand-by feeder takes place when the voltage of the busbar
has subsided to a preset, permissible value. The threshold value for the busbar
voltage for residual voltage transfer is set with setting
Residual voltage limit.
Residual voltage transfer is enabled with setting
Ena Res V transfer.
The connection takes place without assessment of the angle or of the difference
frequency, thus in unsynchronized fashion. Because the voltage of the busbars has
however reached a sufficiently low residual voltage value, the transient effects of
the connection are manageable (momentary jolt, current needed for users to run up
again, voltage reduction).
Main feeder
breaker
Stand-by
feeder breaker
Main feeder
breaker open
command
Stand-by
feeder close
command
1
2
3
4
Figure 946: Signal diagram of residual voltage transfer
1
Busbar voltage
2
Voltage difference between stand-by and busbar voltage
3
Main feeder current
4
Stand-by feeder current
If
DISA_RUN
input is active, transfer is not allowed to complete until input is
deactivated.
1MRS759142 F
Control functions
REX640
Technical Manual
1779
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......