Table 265: Analog inputs
Input
Description
I3P1
1
Three-phase currents
I3P2
1
Three-phase currents
I3P3
1
Three-phase currents
I3P4
1
Three-phase currents
IRES1
1
Residual current (measured or calculated)
IRES2
1
Residual current (measured or calculated)
IRES3
1
Residual current (measured or calculated)
IRES4
1
Residual current (measured or calculated)
See the preprocessing function blocks in this document for the possible
signal sources. The
GRPOFF
signal is available in the function block called
Protection.
3.20.17.5
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "on" and "off".
For this function, the setting is hidden and fixed to "on".
The switch logic depends on inputs
SWITCH_TO2
,
SWITCH_TO3
and
SWITCH_TO4
.
Source 1 is selected as default and switching is done on increased priority.
GRPOFF
signal must be connected to unused current inputs.
GRPOFF
signal is available as output from the Protection function block.
Table 266: Switching operation
Control input signals
Outputs
SWITCH_TO
2
SWITCH_TO
3
SWITCH_TO
4
SOURCE1
SOURCE2
SOURCE3
SOURCE4
Source for
I3P
Source for
IRES
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
I3P1
IRES1
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
I3P2
IRES2
x
1
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
I3P3
IRES3
x
1
x
1
TRUE
FALSE
FALSE
FALSE
TRUE
I3P4
IRES4
If the numbers of channels connected to
I3P1
...
I3P4
and
IRES1
...
IRES4
does not match with the number of connected
SWITCH_TOx
inputs, the
configuration of the function fails.
Outputs
ALARM
and
IRES_ALARM
indicate bad quality data of system measurements
for selected
I3P
and
IRES
, respectively.
Outputs
WARNING
and
IRES_WARNING
indicate questionable quality data of system
measurements for selected
I3P
and
IRES
, respectively.
1
Can be connected to
GRPOFF
1
No difference
1MRS759142 F
Basic functions
REX640
Technical Manual
279
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......