Level detector 2
The calculated compensated unbalance current I_AMPL_COMP is compared to the
set
Alarm start value. If the I_AMPL_COMP exceeds the set Alarm value the Level
detector 2 sends enabling signal to the Alarm control module.
Alarm control
Depending on the
Alarm mode setting, the alarm stage operation is according to
“Normal mode” or “Element counter mode”.
In the “Normal mode” the time characteristic is according to DT. When the
alarm timer has reached the value set by
Alarm delay time, the
ALARM
output is
activated. If the fault disappears before the alarm activates, the alarm timer is reset
immediately.
The “Element counter mode” is used to detect faulty elements of the capacitor bank
and count the number of element failures in each branch and line. On activation, this
module increments the corresponding element failure counters after the set
Alarm
delay time has elapsed.
Blocking logic
There are three operation modes in the blocking function. The operation modes
are controlled by the
BLOCK
input and the global setting Configuration > System >
Blocking mode, which selects the blocking mode. The
BLOCK
input can be controlled
by a binary input, a horizontal communication input or an internal signal of the IED
program. The influence of the
BLOCK
signal activation is preselected with the global
setting
Blocking mode.
The
Blocking mode setting has three blocking methods. In the "Freeze timers"
mode, the operation timer is frozen to the prevailing value. In the "Block all"
mode, the whole function is blocked and the timers are reset. In the "Block
OPERATE output" mode, CUBPTOC operates normally but the
OPERATE
output is
not activated.
4.12.2.6
Application
CUBPTOC is designed for the protection against internal faults in double-Y-
connected capacitor banks. This unbalance protection detects an asymmetry in the
capacitor bank caused by blown fuses or short circuits across bushings or between
capacitor units and the racks in which they are mounted.
Normally, the capacitor units are designed to withstand 110 percent of the nominal
voltage continuously. When an element inside a capacitor bank fails, the remaining
healthier elements experience an increase in voltage across them. If the voltage
exceeds the 110 percent value of the nominal voltage, it can lead to a failure of
the healthier elements of the bank and in turn fail the entire capacitor bank. Since
the capacitor unbalance current is directly proportional to the element failures,
unbalance protection is an effective way of detecting capacitor element failures.
The current unbalance protection function is usually used with the three-phase
capacitor bank overload protection function to increase the sensitivity of protection
for capacitor banks.
Due to the two-stage (operation and alarm stage) unbalance protection and
the natural unbalance compensation facility, the protection of capacitor banks
with internal fuses can be implemented with a very high degree of sensitivity.
Protection functions
1MRS759142 F
1126
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......