9.6.5.1
Energizing check
The Energizing check module checks the energizing direction. Energizing is the
situation where a dead network part is connected to an energized section of the
network. The conditions of the network sections to be controlled by the circuit
breaker, that is, which side has to be live and which side dead, are determined by the
setting
Live dead mode.
Live dead mode can be set in two ways: either through settings or through the
command control.
If the
Live dead mode parameter under the Setting menu is set as
"Command", then
Live dead mode Ctl parameter under the Control menu
can be used to select the values in
. Otherwise, the
Live dead
mode parameter under the Setting menu is used to select the values in
Table 1515: Live dead mode of operation when switching can be carried out
Live dead mode
Description
Off
Live dead mode setting is in off status
Both Dead
Both bus and generator de-energized
Live G, Dead B
Bus de-energized and generator energized
Dead B, G Any
Bus de-energized and generator energized or
de-energized
The actual value for defining the dead bus or generator is given with the
Dead
voltage value setting. Similarly, the actual values of live bus or generator are defined
with the
Live voltage value setting.
When the energizing direction corresponds to the settings, the situation has to
be constant for a time set with the
Energizing time setting before the circuit
breaker closing is permitted. This time delay ensures that the dead side remains
de-energized and that the situation is not caused by a temporary interference. If
the conditions do not persist for a specified operate time, the timer is reset and
the procedure is restarted when the conditions allow it. The circuit breaker does
not close if the measured voltage on the live side is greater than the set value of
Maximum voltage.
The measured energized state is available as a monitored data value ENERG_STATE
and as four function outputs
LBLG
(“Both Live”),
LBDG
(“Live B, Dead G”),
DBLG
(“Dead B, Live G”) and
DBDG
(“Both Dead”), of which only one can be active at a time.
The measured energized state indicates “Unknown” if at least one of the measured
voltages is between the limits set with the dead and live setting parameters.
9.6.5.2
Synchronization check and control
The operation of Synchronization check and control modes can be described with a
module diagram.
Control functions
1MRS759142 F
1560
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......