Figure 879: NSCB2 synchronization
In this application example, breaker NSCB2 must be closed. So the synchronizing
conditions between Bus1 and Bus2 are checked by ASNSCSYN. ASNSCSYN sends
the auto synchronization request and the voltage and frequency difference (ΔU, ΔF)
between Bus1 and Bus2 to ASCGAPC.
ASCGAPC transfers the voltage and frequency difference sent by ASNSCSYN to
the selected ASCGAPC function of source 1 ASGCSYN function. It also sends the
permission to the source to start matching the voltage and frequency. The matching
process is carried out so that the voltage and frequency difference between Bus1
and Bus2 measured by ASNSCSYN reduces and comes within the synchro check
limits. This satisfies the synchro check conditions for breaker NSCB2 which can then
be synchronized by ASNSCSYN. Similarly, the synchronization of NSCB1 and NSCB3
having ASCGAPC is done as shown in
and
.
ASNSCSYN
(NSCB2)
ASGCSYN
(SCB2)
ASGCSYN
(SCB1)
Bus1
Bus2
ASCGAPC
ASNSCSYN
(NSCB1)
ASCGAPC
ASNSCSYN
(NSCB3)
Synchronize
ASCGAPC
ASCGAPC
ASCGAPC
∆
U,
∆
F
∆
U,
∆
F
Matching Start
Source
2
Source
1
NS_ASC_DAT
Figure 880: NSCB1 synchronization
Control functions
1MRS759142 F
1600
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......