Table 842: Voltages and currents used for induced voltage (emf) E calculation
Voltage selection
setting
Phase
supervision
setting
Calculation of internal induced voltage (emf) E
1
phase-to-earth
A or AB
E
U
I
j X
A
A
leak
=
⋅
+
⋅
⋅
(
)
3
(
)
(Equation 240)
phase-to-earth
B or BC
E
U
I
j X
B
B
leak
=
⋅
+
⋅
⋅
(
)
3
(
)
(Equation 241)
phase-to-earth
C or CA
E
U
I
j X
C
C
leak
=
⋅
+
⋅
⋅
(
)
3
(
)
(Equation 242)
phase-to-phase
A or AB
E
U
I
I
j X
AB
A
B
leak
=
+
−
⋅
⋅
(
)
(
) (
)
(Equation 243)
phase-to-phase
B or BC
E
U
I
I
j X
BC
B
C
leak
=
+
−
⋅
⋅
(
)
(
) (
)
(Equation 244)
phase-to-phase
C or CA
E
U
I
I
j X
CA
C
A
leak
=
+
−
⋅
⋅
(
)
(
) (
)
(Equation 245)
Pos sequence
N/A
E
U
I
j X
leak
=
⋅
+
⋅
⋅
(
)
3
1
1
(
)
(Equation 246)
If all three phase or phase-to-phase voltages and phase currents
are fed to the protection relay, the positive-sequence alternative is
recommended.
If the leakage reactance of the protected equipment is unknown or if the
measured voltage (U
m
) is to be used in the excitation level calculation,
then by setting the leakage reactance value to zero the calculated
induced voltage (E) is equal to the measured voltage.
The calculated U/f ratio is scaled to a value based on the nominal U
n
/f
n
ratio.
However, the highest allowed continuous voltage (in % U
n
) can be defined by
setting the parameter
Voltage Max Cont to change the basis of the voltage. The
measured voltage is compared to the new base value to obtain the excitation level.
1
Voltages, currents and the leakage reactance X
leak
in the calculations are given in volts, amps and
ohms.
1MRS759142 F
Protection functions
REX640
Technical Manual
887
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......