the whole function is blocked and the timers are reset. In the "Block OPERATE
output" mode, the function operates normally but the
OPERATE
output is not
activated.
4.8.1.6
Application
The task of a generator in a power plant is to convert mechanical energy into
electrical energy. Sometimes the mechanical power from the prime mover may
decrease so much that it does not cover the internal losses. The task of an
underpower protection is to protect the generator from very low power output
conditions.
Steam turbines become easily overheated if the steam flow becomes too low or if
the steam ceases to flow through the turbine. Hydro turbine of the Kaplan type may
be damaged due to the fact that the turbine blade surfs on the water and sets up
axial pressure on the bearing. Diesel engines may be damaged due to insufficient
lubrication.
If the generator size is very large, it is uneconomical to continue running it with
low generated power. In the reverse power condition, large generators draw a
considerable amount of power from the rest of the system to feed their internal
losses. Hence, it is desirable to disconnect the generator in such situations.
In case of the parallel-connected generators, for example, the load of one generator
may be so low that it is better to disconnect it and let the remaining generators
feed the network.
Where a low value of power setting is required, for example less than
2%, the correction parameters should be used to compensate for the
measuring errors. The manufacturer of the measuring devices is to be
contacted for information on the measuring errors.
If the measuring errors are not compensated for, the underpower setting
should not be lower than the sum of the current-measuring and voltage-
measuring errors.
For example, if the error of the current-measuring device is 2% and that
of the voltage-measuring device is 1%, the minimum setting is (2 + 1)% =
3%.
4.8.1.7
Signals
DUPPDPR Input signals
Table 992: DUPPDPR Input signals
Name
Type
Default
Description
I3P
SIGNAL
-
Three-phase currents
U3P
SIGNAL
-
Three-phase voltages
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
DISABLE
BOOLEAN
0=False
Signal to block the
function during gen-
erator startup
Protection functions
1MRS759142 F
1060
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......