Table 940: OOSRPSB Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Zone 1 reach
1...100
%
1
70
Percent of Mho for-
ward reach indicat-
ing the end of zone
1 and the beginning
of zone 2
Max number slips
1...10
1
1
Number of pole
slips before operat-
ing zone 1
Max Num slips Zn2 1...20
1
1
Number of pole
slips before operat-
ing zone 2
Max Num slips Zn3 1...20
1
1
Number of pole
slips before operat-
ing zone 3
Operate delay time 20...60000
ms
10
300
Delay after OOS op-
erate detected
Operate dropout
time
20...60000
ms
10
100
Time operate out-
put remains active
V dip time
500...5000
ms
10
2000
Maximum allowable
time for voltage to
dip
Zone 2 enable
1=Yes
0=No
0=No
Enable zone 2 fea-
ture
Zone 3 enable
1=Yes
0=No
0=No
Enable zone 3 fea-
ture
Table 941: OOSRPSB Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 942: OOSRPSB Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Min Ps Seq current 0.01...10.00
xIn
0.01
0.10
Minimum positive
sequence current
for operation
Max Ng Seq current 0.01...10.00
xIn
0.01
0.20
Maximum negative
sequence current
for operation
Breaker open time
0...300
ms
1
30
Opening time of
the breaker
Disable time
20...60000
ms
10
5000
Additional time
function is disabled
after removal of
DISABLE input
Reset time
20...60000
ms
10
5000
Time to reset
OOS condition and
counters
Voltage reversal
0=No
1=Yes
0=No
Rotate voltage sig-
nals by 180 degrees
Protection functions
1MRS759142 F
1014
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......