Table 659: TR2PTDF Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Enable high set
0=False
1=True
1=True
Enable high set
stage
Slope section 3
10...100
%
1
100
Slope of the third
line of the operat-
ing characteristics
Harmonic deblock
2.
0=False
1=True
1=True
2. harmonic de-
blocking in case of
switch on to fault
Stop value 5.H
10...50
%
1
35
5. harmonic de-
blocking ratio
Harmonic deblock
5.
0=False
1=True
0=False
5. harmonic de-
blocking in case of
severe overvoltage
Table 660: TR2PTDF Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off/On
CT connection type 1=Type 1
2=Type 2
1=Type 1
CT connection
type. Determined
by the directions of
the connected cur-
rent transformers
Winding 1 type
1=Y
2=YN
3=D
4=Z
5=ZN
1=Y
Connection of the
HV side windings
Winding 2 type
1=y
2=yn
3=d
4=z
5=zn
1=y
Connection of the
LV side windings
Clock number
0=Clk Num 0
1=Clk Num 1
2=Clk Num 2
4=Clk Num 4
5=Clk Num 5
6=Clk Num 6
7=Clk Num 7
8=Clk Num 8
10=Clk Num 10
11=Clk Num 11
0=Clk Num 0
Setting the phase
shift between HV
and LV with clock
number for connec-
tion group com-
pensation (e.g.
Dyn11 -> 11)
Zro A elimination
1=Not eliminated
2=Winding 1
3=Winding 2
4=Winding 1 and 2
1=Not eliminated
Elimination of the
zero-sequence cur-
rent
CT ratio Cor Wnd 1
0.40...4.00
0.01
1.00
CT ratio correction,
winding 1
CT ratio Cor Wnd 2
0.40...4.00
0.01
1.00
CT ratio correction,
winding 2
Protection functions
1MRS759142 F
712
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......