The calculation window length is set with the
Sliding interval setting. It has three
window lengths ("3 seconds", "1 minute" or "5 minutes") for sliding mean value
outputs. Output values can also be seen in monitoring.
The window type used for configuration tool output values is always sliding. Output
values are updated once every 0.1 seconds.
Figure 961: Sliding 3 seconds value calculation in principle
The sliding mean values of the fundamental of each phase are
SMNH01_A
,
SMNH01_B
and
SMNH01_C
. Actual harmonics are seen with their number, for example, phase A
for second harmonic is
SMNH02_A
and phase C for 9
th
harmonic is
SMNH09_C
. Direct
current component outputs are
SMNDC_A
,
SMNDC_B
and
SMNDC_C
.
Intervals that are longer than 3 seconds are calculated using free running 3-second
mean values.
The longer 10-minute mean values of the fundamental of each phase are seen in
monitored data as LMNH01_A, LMNH01_B and LMNH01_C. Actual harmonics are
seen with their number. Direct current components are LMNDC_A, LMNDC_B and
LMNDC_C.
Time stamps for ready 10-minute mean value calculation can be seen in the
monitored data L time stamp.
The window type used for the 10-minute mean value calculation is always non-
sliding. The 10-minute value calculation begins based on the protection relay's
internal clock 10 minutes time (for example,11:00, 11:10, 11:20, 11:30, 11:40, 11:50,
12:00…). This is called 10 min tick.
1MRS759142 F
Power quality measurement functions
REX640
Technical Manual
1811
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......