
~
R
F
/2
R
1
X
1
R
X
X
1
R
1
R
F
/2
Figure 540: The fault loop impedance model for phase-to-phase impedance
measuring elements
R
1
Positive-sequence resistance from measuring point to fault location.
X
1
Positive-sequence reactance from measuring point to fault location.
R
F
Physical fault resistance between phases, for example, arc resistance.
The phase-to-phase impedance measuring elements measure only half
of the physical fault resistance between phases. This must be taken into
account when the resistive reach of the phase-to-phase elements is set
(that is, setting the value of 5 Ω corresponds 5+5=10 Ω of physical arc
resistance between phases).
The resistive reach setting is common for phase-to-phase and three-phase
impedance measuring elements.
The operation time delay is defined with the setting
PP operate delay Znx (x =
1... 5). The timer can be disabled with the setting
PP Op delay Mod Znx = "False".
This blocks the
OPERATE_Zx
(x = 1... 5) output of the phase-to-phase measuring
elements.
Three-phase impedance measuring element
DSTPDIS has a dedicated measuring element for a three-phase short circuit fault
for each zone. The three-phase measuring element uses the positive-sequence
quantities for a fault loop impedance estimation which increases the accuracy by
reducing the influence of line parameter asymmetry. This is advantageous especially
in case of non-transposed, asymmetrical lines. The three-phase impedance
measuring element is enabled together with the phase-to-phase impedance
elements by the setting
Op Mod PP loops Znx (x = 1... 5) = "True".
The reach of the three-phase measuring element is based on the loop impedance
Three-phase measuring element reach = Z + R = R + j
1
F
1
X
X + R
1
F
(Equation 269)
Protection functions
1MRS759142 F
968
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......