4.12.5.2
Function block
Figure 641: Function block
4.12.5.3
Functionality
The compensated neutral unbalance voltage protection function CNUPTOV detects
overvoltage at the neutral point of the shunt capacitor. A blown fuse or a
shortcircuited capacitor element results in unbalance in the shunt capacitor bank
causing increase in neutral point voltage. With CNUPTOV, an inherent capacitor
bank unbalance which results in non-zero neutral point voltage can be compensated
automatically on a continuous basis.
The function starts when the fundamental (DFT) component of the compensated
neutral unbalance voltage exceeds the set limit. CNUPTOV operates with the
definite time (DT) characteristics.
The function contains a blocking functionality. It is possible to block function
outputs, the definite timer or the function itself.
4.12.5.4
Analog channel configuration
CNUPTOV has three analog group inputs which must be properly configured.
Table 1094: Analog inputs
Input
Description
U3P
Three phase voltages
URES
Residual voltage (measured or calculated)
UNEUT
Measured neutral voltage
See the preprocessing function blocks in this document for the possible
signal sources.
There are a few special conditions which must be noted with the configuration.
Table 1095: Special conditions
Condition
Description
U3P connected real meas-
urements
The function can work with any two voltage channels connec-
ted but it is recommended to connect all three voltage chan-
nels.
URES calculated
The function requires that all three voltage channels from ter-
minal side are connected to calculate residual voltage. Setting
VT connection
must be "Wye" in that particular UTVTR.
1MRS759142 F
Protection functions
REX640
Technical Manual
1149
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......