The excitation level (M) can be calculated:
M
E
f
U
f
Volt Max continuous
m
n
n
=
⋅
100
(Equation 247)
M
excitation level (U/f ratio or volts/hertz) in pu
E
internal induced voltage (emf)
f
m
measured frequency
U
n
nominal phase-to-phase voltage
f
n
nominal frequency
If the input frequency (f
m
) is less than 20 percent of the nominal frequency (f
n
), the
calculation of the excitation level is disabled and forced to zero value. This means
that the function is blocked from starting and operating during a low-frequency
condition.
The calculated excitation level (U/f ratio or volts/hertz) VOLTPERHZ is available in
the Monitored data view.
Level detector
Level detector compares the calculated excitation level to the
Start value setting. If
the excitation level exceeds the set limit, the module sends an enabling signal to
start Timer.
Timer
Once activated, Timer activates the
START
output. Depending on the value of the
Operating curve type setting, the time characteristics are according to DT or IDMT.
When the operation timer has reached the value set by
Operate delay time in the
DT mode or the value defined by the inverse time curve, the
OPERATE
output is
activated.
In a drop-off situation, that is, when the excitation level drops below
Start value
before the function operates, the reset timer is activated and the
START
output
resets after the time delay of
Reset delay time for the DT characteristics. For
the IDMT curves, the reset operation is as described in
For the IDMT curves, it is possible to define the maximum and minimum operating
times via the
Minimum operate time and Maximum operate time settings. The
Maximum operate time setting is used to prevent infinite start situations at low
degrees of overexcitation. The
Time multiplier setting is used for scaling the IDMT
operate times.
The activation of the
OPERATE
output activates the
BLK_RESTART
output.
For the DT characteristics, the deactivation of the
OPERATE
output activates the
cooling timer. The timer is set to the value entered in the
Cooling time setting. The
BLK_RESTART
and
COOL_ACTIVE
outputs are kept active until the cooling timer is
reset. If the excitation increases above the set value during this period, the
OPERATE
output is activated immediately. For IDMT, the deactivation of
BLK_RESTART
and
COOL_ACTIVE
depends on the curve type selected.
Protection functions
1MRS759142 F
888
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......