The
T_ENARESTART
output indicates in seconds the duration for which the
BLK_RESTART
output still remains active. The value is available in the Monitored
data view.
Timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operating time. The value is
available in the Monitored data view.
Blocking logic
There are three operation modes in the blocking functionality. The operation
modes are controlled by the
BLOCK
input and the global setting Configuration >
System > Blocking mode which selects the blocking mode. The
BLOCK
input can be
controlled by a binary input, a horizontal communication input or an internal signal
of the protection relay's program. The influence of the
BLOCK
signal activation is
preselected with the global setting
Blocking mode.
The
Blocking mode setting has three blocking methods. In the "Freeze timers"
mode, the operation timer is frozen to the prevailing value. In the "Block all" mode,
the whole function is blocked and the timers are reset. In the "Block OPERATE
output" mode, the function operates normally but the
OPERATE
output is not
activated.
4.5.7.6
Timer characteristics
OEPVPH supports both DT and IDMT characteristics. The DT timer characteristics
can be selected as "ANSI Def. Time" or "IEC Def. Time" in the
Operating curve type
setting. The functionality is identical in both cases. When the DT characteristics
are selected, the functionality is only affected by the
Operate delay time and Reset
delay time settings.
OEPVPH also supports four overexcitation IDMT characteristic curves: "OvExt IDMT
Crv1", "OvExt IDMT Crv2", "OvExt IDMT Crv3" and "OvExt IDMT Crv4".
Overexcitation inverse definite minimum time curve (IDMT)
In the inverse time modes, the operate time depends on the momentary value of the
excitation: the higher the excitation level, the shorter the operate time. The operate
time calculation or integration starts immediately when the excitation level exceeds
the set
Start value and the
START
output is activated.
The
OPERATE
output is activated when the cumulative sum of the integrator
calculating the overexcitation situation exceeds the value set by the inverse time
mode. The set value depends on the selected curve type and the setting values
used.
The
Minimum operate time and Maximum operate time settings define the
minimum operate time and maximum operate time possible for the IDMT mode.
For setting these parameters, a careful study of the particular IDMT curves is
recommended.
The operation time of the function block can vary much between
different operating curve types even if other setting parameters for the
curves were not changed.
Once activated, the Timer activates the
START
output for the IDMT curves. If the
excitation level drops below the
Start value setting before the function operates,
the reset timer is activated and the
START
output resets immediately. If
START
1MRS759142 F
Protection functions
REX640
Technical Manual
889
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......