8.1.3
Measurement function applications
The measurement functions are used for power system measurement, supervision
and reporting to LHMI, a monitoring tool within PCM600, or to the station level,
for example, with IEC 61850. The possibility to continuously monitor the measured
values of active power, reactive power, currents, voltages, power factors and so on,
is vital for efficient production, transmission, and distribution of electrical energy.
It provides a fast and easy overview of the present status of the power system to
the system operator. Additionally, it can be used during testing and commissioning
of protection and control protection relays to verify the proper operation and
connection of instrument transformers, that is, the current transformers (CTs) and
voltage transformers (VTs). The proper operation of the protection relay analog
measurement chain can be verified during normal service by a periodic comparison
of the measured value from the protection relay to other independent meters.
When the zero signal is measured, the noise in the input signal can still produce
small measurement values. The zero point clamping function can be used to ignore
the noise in the input signal and, hence, prevent the noise to be shown in the user
display. The zero clamping is done for the measured analog signals and angle values.
The demand values are used to neglect sudden changes in the measured analog
signals when monitoring long time values for the input signal. The demand values
are linear average values of the measured signal over a settable demand interval.
The demand values are calculated for the measured analog three-phase current
signals.
The limit supervision indicates, if the measured signal exceeds or goes below the
set limits. Depending on the measured signal type, up to two high limits and up to
two low limits can be set for the limit supervision.
The deadband supervision reports a new measurement value if the input signal
has gone out of the deadband state. The deadband supervision can be used in
value reporting between the measurement point and operation control. When the
deadband supervision is properly configured, it helps to keep the communication
load to a minimum and yet measurement values are reported frequently enough.
The instantaneous measurement values of several measurement functions are
available as primary values for further use in Application Configuration. The current
values are in amperes while voltage values are in kilovolts and power values in
kilovolt-amperes, watts or volt-amperes reactive.
8.1.4
Three-phase current measurement CMMXU (ANSI IA, IB, IC)
8.1.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase current measurement
CMMXU
3I
IA, IB, IC
Measurement functions
1MRS759142 F
1442
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......