
The function can operate correctly with only two phase-to-earth voltages if the
residual voltage is also measured and connected to the source UTVTR which
provides the phase-to-earth voltages to the function. In this case, the missing
phase-to-earth voltage is correctly calculated internally in the relay. If the measured
residual voltage is connected to SCEFRFLO input
URES
,
Phase voltage Meas can be
set to "Accurate".
When the
Phase voltage Meas setting is set to "Ph-to-ph without Uo" and only
phase-to-phase voltages are available (but not Uo), only short-circuit measuring
loops (fault loops “AB Fault”, “BC Fault”, “CA Fault” or “ABC Fault”) can be measured
accurately. In this case, the earth-fault loops (fault loops “AG Fault”, “BG Fault” or
“CG Fault”) cannot provide correct fault distance estimates and the triggering of the
function in case of an earth fault is automatically disabled. The situation is similar if
only two phase-to-earth voltages are measured and the measured residual voltage
is not connected to SCEFRFLO.
5.7.7
Application
The main objective of the feeder terminals is a fast, selective and reliable operation
in faults inside the protected feeder. In addition, information on the distance to
the fault point is very important for those involved in operation and maintenance.
Reliable information on the fault location greatly decreases the downtime of the
protected feeders and increases the total availability of a power system.
SCEFRFLO provides impedance-based fault location. It is designed for radially
operated distribution systems and is applicable for locating short circuits in all
kinds of distribution networks. Earth faults can be located in effectively earthed and
low-resistance/low-reactance earthed networks. With certain limitations, SCEFRFLO
can also be used for locating an earth fault in unearthed distribution networks.
Configuration example
A typical configuration example for SCEFRFLO triggering is illustrated in
where external triggering is applied, that is,
Calculation Trg mode is set to
“External”. The
OPERATE
signal from non-directional overcurrent function PHLPTOC
is used to provide an indication of a short circuit fault. The
OPERATE
signal from
the directional earth-fault function DEFLPDEF is used to provide an indication of an
earth fault at the protected feeder.
SCEFRFLO with the autoreclosing function
When SCEFRFLO is used with the autoreclosing sequence, the distance estimate
from the first trip is typically the most accurate one. The fault distance estimates
from successive trips are possible but accuracy can be decreased due to inaccurate
load compensation. During the dead time of an autoreclosing sequence, the load
condition of the feeder is uncertain.
The triggering of SCEFRFLO can also be inhibited during the autoreclosing
sequence. This is achieved by connecting the signal
ACTIVE
from the autoreclosing
function DARREC, which indicates that the autoreclosing sequence is in progress,
to the
BLOCK
input of SCEFRFLO. Blocking of the SCEFRFLO triggering is indicated
during the autoreclosing sequence when the load compensation or steady-state
asymmetry elimination is based on the delta quantities. This applies to the short
circuit faults when
Load Com PP loops is set to "Enabled" or, to earth faults, when
EF algorithm Sel is set to "Load compensation" or "Load modelling".
1MRS759142 F
Protection related functions
REX640
Technical Manual
1217
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......