
must therefore be based on the real part of the measured admittance,
that is, conductance. Thus, the best selectivity is achieved when the
compensated network is operated either in the undercompensated or
overcompensated mode.
For example, in a 15 kV compensated network, the magnitude of the earth-fault
current of the protected feeder is 10 A (Rf = 0 Ω) and the magnitude of the network
is 100 A (Rf = 0 Ω). During an earth fault, a 15 A resistor is connected in parallel to
the coil after a 1.0 second delay. Compensation degree is overcompensated, K = 1.1.
During an earth fault in the forward direction, that is, inside the protected feeder,
the theoretical value for the measured admittance after the connection of the
parallel resistor can be calculated.
Yo
I
j
I
K
I
U
A
j
A
A
Rcc
eTot
eFd
ph
≈
+ ⋅
⋅
−
(
)
−
(
)
=
+ ⋅
⋅
−
(
)
−
(
)
1
15
100
1 1 1
10
15
.
kkV
j
3
1 73
2 31
≈
− ⋅
(
)
.
.
milliSiemens
(Equation 68)
Before the parallel resistor is connected, the resistive part of the measured
admittance is due to the leakage losses of the background network and the losses
of the coil. As they are typically small, the resistive part may not be sufficiently large
to secure the discrimination of the fault and its direction based on the measured
conductance. This and the rating and the operation logic of the parallel resistor
should be considered when setting the admittance characteristic.
When a high sensitivity of the protection is required, the residual current
should be measured with a cable/ring core CT, that is, the Ferranti CT.
Also the use of the sensitive
Io
input should be considered. The residual
voltage measurement should be done with an open delta connection of
the three single pole-insulated voltage transformers.
The sign of the admittance characteristic settings should be considered
based on the location of characteristic boundary in the admittance plane.
All forward-settings are given with positive sign and reverse-settings
with negative sign.
Operation characteristic
After the admittance calculation is released, the calculated neutral admittance is
compared to the admittance characteristic boundaries in the admittance plane. If
the calculated neutral admittance Yo moves outside the characteristic, the enabling
signal is sent to the timer.
EFPADM supports a wide range of different characteristics to achieve the maximum
flexibility and sensitivity in different applications. The basic characteristic shape
is selected with the
Operation mode and Directional mode settings. Operation
mode defines which operation criterion or criteria are enabled and Directional mode
defines if the forward, reverse or non-directional boundary lines for that particular
operation mode are activated. The
FAULT_DIR
output indicates which operation
sector the fault is measured. The output is operational once the function is started.
Protection functions
1MRS759142 F
498
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......