In direct operation, a single message is used to initiate the control action of a
physical device. The direct operation method uses less communication network
capacity and bandwidth than the SBO method, because the procedure needs fewer
messages for accurate operation.
The “status-only” mode means that control is not possible (non-controllable) via
communication or from LHMI. However, it is possible to control a disconnector
(DCXSWI) from
AU_OPEN
and
AU_CLOSE
inputs.
AU_OPEN
and
AU_CLOSE
control the object directly regardless of the set
Control model. These inputs can be used when control is wanted to be
implemented purely based on ACT logic and no additional exception
handling is needed. However, in case of simultaneous open and close
control, the open control is always prioritized.
1. Send reservationto other terminals
2. Receive response
Selected
to operate
REF 615
REF 615
REF 615
REF 615
REF 615
Figure 829: Control procedure in the SBO method
Local/Remote operations
The local/remote selection affects CBXCBR, DCXSWI and ESXSWI.
• Local: the opening and closing via communication is disabled.
• Remote: the opening and closing via LHMI is disabled.
•
AU_OPEN
and
AU_CLOSE
inputs function regardless of the local/remote selection.
9.1.5
Application
In the field of distribution and sub-transmission automation, reliable control and
status indication of primary switching components both locally and remotely is
in a significant role. They are needed especially in modern remotely controlled
substations.
1MRS759142 F
Control functions
REX640
Technical Manual
1511
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......