Manual
blocking
type
Enumeration
Description
5
EXT
External blocking has an effect in the manual operation mode
6
OC, EXT
Conditions 2 and 5 together: Load current and external block-
ing have effect in the manual operation mode
7
UV, EXT
Conditions 3 and 5 together: Block lowering (under) voltage
and external blocking have effect in the manual operation
mode
8
OC, UV, EXT
All conditions 2, 3 and 5 together: Load current and block
lowering (under) voltage and external blocking have effect in
the manual operation mode
If the
Custom Man blocking setting is "Custom disabled", the blocking schema
regarding the acting operation mode "Manual" or “Parallel manual” is as given in
. Other operation modes follow the default schema.
Table 1577: Blocking schema for selection "Custom disabled"
Active
operation
mode
Comman
d
Load
current
Block
lower
voltage
Runback
raise
voltage
High
circulatin
g current
External
block
Extreme
positions
Manual,
Parallel
manual
Raise
x
x
Lower
x
Table 1578: Blocking schema for selection "OC, UV, EXT"
Active
operation
mode
Comman
d
Load
current
Block
lower
voltage
Runback
raise
voltage
High
circulatin
g current
External
block
Extreme
positions
Manual,
Parallel
manual
Raise
x
x
x
x
x
Lower
x
x
x
x
Table 1579: Blocking schema for selection “UV, EXT”
Active
operation
mode
Comman
d
Load
current
Block
lower
voltage
Runback
raise
voltage
High
circulatin
g current
External
block
Extreme
positions
Manual,
Parallel
manual
Raise
x
x
x
x
Lower
x
x
x
Load current
The load current blocking is mainly used for preventing the tap changer from
operating in an overcurrent situation. For example, if the current is not high enough
to activate the protection relay of the substation, it can still be fatal for the
diverter switch of the tap changer. This operation can be adjusted with the setting
Control functions
1MRS759142 F
1718
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......