Circuit breaker closing time measurement, “From Pos to Curr”
“From Pos to Curr” measures the closing time from position change indicated by
auxiliary contacts till current is flowing in the primary circuit.
This operation mode requires that current signal is connected to
I3P1
and
I3P2
inputs. This mode is recommended only for supervision
purposes to alarm incase breaker doesn’t close properly, not to measure
actual travelling time.
Circuit breaker opening time measurement
From the function operation point of view the opening time measurement is not
as important as closing time. Hence the opening time is always measured in “From
Cmd to Pos” mode which would provide accurate enough information.
9.12.5.8
Recorded data
The transfer related information is stored when the Recorded data module is
triggered. This happens when
Decoupling delay time is elapsed after TR_RUNNING
signal goes from TRUE to FALSE. Three sets of recorded data are available in total
for each of the measurement. The sets are saved in data banks 1-3.
The data bank 1 of the respective measurement holds the most recent recorded
data. Older data are moved to the subsequent banks (1→2 and 2→3). When all
three banks have data of a respective measurement and there is a new transfer
complete operation, the latest data set is placed into bank 1 and the data in bank 3
is overwritten by the data from bank 2.
The recorded data can be reset with the RESET_REC binary input, from Clear menu
or via communication.
Table 1605: Recorded data
Parameter
Type
Description
Transfer mode
ENUM
Transfer mode
Transfer direction
ENUM
Transfer direction
Transfer cause
ENUM
Cause of transfer
Transfer failure
ENUM
Transfer failure cause
Transfer time
TimeStamp
The time at which the close
command is issued for trans-
fer
Transfer Dur
INT
Time between transfer initia-
tion and CB close command
Busbar Max dv/dt
REAL
Maximum rate of change of
busbar voltage
Busbar Max df/dt
REAL
Maximum rate of change of
frequency of busbar voltage
Table continues on the next page
1MRS759142 F
Control functions
REX640
Technical Manual
1785
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......