Table 62: Optional operation modes for setting group selection
SG operation mode
Description
Operator (Default)
Setting group can be changed with the setting Settings/Set-
ting group/Active group. Value of the
SG_LOGIC_SEL
out-
put is FALSE.
Logic mode 1
Setting group can be changed with binary inputs
(
BI_SG_2
...
BI_SG_6
). The highest TRUE binary input de-
fines the active setting group. Value of the
SG_LOGIC_SEL
output is TRUE.
Logic mode 2
Setting group can be changed with binary inputs where
BI_SG_4
is used for selecting setting groups 1–3 or 4–6.
When binary input
BI_SG_4
is FALSE, setting groups 1–3 are
selected with binary inputs
BI_SG_2
and
BI_SG_3
. When
binary input
BI_SG_4
is TRUE, setting groups 4–6 are selec-
ted with binary inputs
BI_SG_5
and
BI_SG_6
. Value of the
SG_LOGIC_SEL
output is TRUE.
For example, six setting groups can be controlled with three binary inputs.
SG
operation mode is set to "Logic mode 2" and inputs
BI_SG_2
and
BI_SG_5
are
connected together the same way as inputs
BI_SG_3
and
BI_SG_6
.
Table 63: SG operation mode = "Logic mode 1"
Input
BI_SG_2
BI_SG_3
BI_SG_4
BI_SG_5
BI_SG_6
Active group
FALSE
FALSE
FALSE
FALSE
FALSE
1
TRUE
FALSE
FALSE
FALSE
FALSE
2
any
TRUE
FALSE
FALSE
FALSE
3
any
any
TRUE
FALSE
FALSE
4
any
any
any
TRUE
FALSE
5
any
any
any
any
TRUE
6
Table 64: SG operation mode = "Logic mode 2"
Input
BI_SG_2
BI_SG_3
BI_SG_4
BI_SG_5
BI_SG_6
Active group
FALSE
FALSE
FALSE
any
any
1
TRUE
FALSE
FALSE
any
any
2
any
TRUE
FALSE
any
any
3
any
any
TRUE
FALSE
FALSE
4
any
any
TRUE
TRUE
FALSE
5
any
any
TRUE
any
TRUE
6
Setting group 1 can be copied to any other or all groups from HMI (Copy group 1).
Basic functions
1MRS759142 F
132
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......