Timer 1
Once activated, the timer activates the alarm timer. The timer characteristic is
according to DT. When the alarm timer has reached the value set by
Alarm delay
time, the
ALARM
output is activated.
If the fault disappears before the alarm activates, the alarm timer is reset
immediately.
Timer 2
Once activated, the timer activates the operation timer. The timer characteristic is
according to DT. When the operation timer has reached the value set by
Operate
delay time, the
OPERATE
output is activated.
If the fault disappears before the operate activates, the operation timer is reset
immediately.
If the input
RESO_IN
becomes active, the
OPERATE
output is activated immediately.
If the resonance protection at a higher-order filter branch has already operated,
the function in lower-order filter branches can be tripped immediately using this
feature.
Blocking logic
There are three operation modes in the blocking function. The operation modes
are controlled by the
BLOCK
input and the global setting Configuration > System >
Blocking mode which selects the blocking mode. The
BLOCK
input can be controlled
by a binary input, a horizontal communication input or an internal signal of the IED
program. The influence of the
BLOCK
signal activation is preselected with the global
setting
Blocking mode.
The
Blocking mode setting has three blocking methods. In the “Freeze timers”
mode, the operation timer is frozen to the prevailing value. In the “Block all”
mode, the whole function is blocked and the timers are reset. In the “Block
OPERATE output” mode, SRCPTOC operates normally but the
OPERATE
output is
not activated.
4.12.4.6
Application
Switched shunt capacitor banks are widely used by utilities and customers in
industrial distribution systems to provide voltage support and to improve the
power factor of a load. Capacitor steps may be switched in and out of circuits
routinely as the demand for capacitive VAR compensation of a load fluctuates.
Normally, automatic power factor controllers are employed which automatically
switch on or off the capacitors of the capacitor bank, depending upon the prevalent
reactive power requirement in the system.
One potential problem for the application of automatic power factor controllers is
that it may cause harmonic resonance under certain system conditions. Capacitor
switching changes the parameters of the system, which may cause the resonance
frequency of the circuit to be equal to one of the frequencies of the harmonic
sources prevalent in the system. Harmonic resonance, when it occurs, may result
in severe voltage and current distortions, which increases losses and causes
overheating of other equipment in the circuit.
A traditional way of solving the problem is to conduct a detailed system study for
each individual installation and use the results to properly size the capacitors and
determine the right operating range of capacitors to avoid harmonic resonance
1MRS759142 F
Protection functions
REX640
Technical Manual
1145
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......