8.1.2
Measurement functionality
The functions can be enabled or disabled with the
Operation setting. The
corresponding parameter values are "On" and "Off".
Some of the measurement functions operate on two alternative measurement
modes: "DFT" and "RMS". The measurement mode is selected with the
X
Measurement mode setting. Depending on the measuring function if the
measurement mode cannot be selected, the measuring mode is "DFT".
Demand value calculation
The demand values are calculated separately for each measurement function
and per phase when applicable. The available measurement modes are "Linear"
and "Logarithmic". The "Logarithmic" measurement mode is only effective for
phase current and residual current demand value calculations. The demand
value calculation mode is selected with the setting parameter Configuration >
Measurements > A demand Av mode. The time interval for all demand
value calculations is selected with the setting parameter Configuration >
Measurements > Demand interval.
The demand time interval is synchronized to the real-time clock of the protection
relay. When the demand time interval or calculation mode is changed, it initializes
the demand value calculation. For the very first demand value calculation interval,
the values are stated as invalid until the first refresh is available.
The "Linear" calculation mode uses the periodic sliding average calculation of the
measured signal over the demand time interval. A new demand value is obtained
once in a minute, indicating the analog signal demand over the demand time
interval proceeding the update time. The actual rolling demand values are stored
in the memory until the value is updated at the end of the next time interval.
The "Logarithmic" calculation mode uses the periodic calculation using a log10
function over the demand time interval to replicate thermal demand ammeters. The
logarithmic demand calculates a snapshot of the analog signal every 1/15 x demand
time interval.
Each measurement function has its own recorded data values. In protection relay,
these are found in Monitoring > Recorded data > Measurements. In the technical
manual these are listed in the monitored data section of each measurement
function. These values are periodically updated with the maximum and minimum
demand values. The time stamps are provided for both values.
Reset of Recorded data initializes a present demand value to the minimum and
maximum demand values.
Value reporting
The measurement functions are capable of reporting new values for network control
center (SCADA system) based on various functions.
• Zero-point clamping
• Deadband supervision
• Limit value supervision
In the three-phase voltage measurement function VMMXU the
supervision functions are based on the phase-to-phase voltages.
However, the phase-to-earth voltage values are also reported with the
phase-to-phase voltages.
Measurement functions
1MRS759142 F
1434
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......