When the
Voltage selection setting is “Positive Seq”, the positive-sequence
component is compared with the set
Voltage start value. If it is lower than the set
Voltage start value, the
START
output is activated.
Once
START
is activated, the function monitors the behavior of the voltage defined
by
Voltage selection setting with the defined LVRT curve. When defined voltage
enters the operating area, the
OPERATE
output is activated instantaneously. The
pulse length of
OPERATE
is fixed to 100 ms.
START
also deactivates along with
OPERATE
.
If a drop-off situation occurs, that is, voltage restores above
Voltage start value,
before
OPERATE
is activated, the function does not reset until maximum recovery
time under consideration has elapsed, that is,
START
output remains active.
LVRT curve is defined using time-voltage settings coordinates. The settings
available are
Recovery time 1… Recovery time 10 and Voltage level 1… Voltage level
10. The number of coordinates required to define a LVRT curve is set by Active
coordinate settings.
When
Recovery time 1 is set to non-zero value, it results into horizontal
characteristics from point of fault till
Recovery time 1.
Two examples of LVRT curve are defined in
with
corresponding settings in
It is necessary to set the coordinate points correctly in order to avoid
maloperation. For example, setting for
Recovery time 2 should be greater
than
Recovery time 1. Recovery time 1… Recovery time 10 are the
respective time setting from the point of fault.
Figure 504: Low voltage ride through example curve A
Protection functions
1MRS759142 F
902
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......