
4.7.5.6
Application
The directional negative sequence impedance function is normally used on
incoming line or feeder connected to the busbar, which is made to operate in the
specified direction for secured operation. The fault direction can be either referred
as forward or reverse of the relay.
There are different directional elements used to determine the direction of
faults, one such element is negative sequence impedance. The calculated negative
sequence impedance is sensitive enough to identify fault in power system networks
with strong source where less negative-sequence voltage and current will be present
during faults.
By using suitable restraint factor, it is also possible to avoid false tripping with
systems having un-transposed lines where some default negative sequence current
will be present during normal operation.
Application example
Relay setting calculation for the DNZPDIS function is shown with below application
example of parallel lines with two end sources of power system network.
G
G
Line 1
Line 2
DNZPDIS
CB1
CB3
CB4
CB2
Forward fault
Reverse fault
3
Figure 580: Power system network with parallel line and two sources
Setting value calculation
Line parameters:
Resistance = 0.126 ohm/km
Reactance = 0.600 ohm/km
Line length = 100 km
Total impedance (Z
1
tot) of line1 or line2 is calculated below
= 12.6 + j60.1 in ohm
Z
1
tot = (0.126 + j0.60 ohm/km) * 100 km
(Equation 279)
Magnitude of positive sequence impedance (Z
1
tot) = 60.4 ohm. The following
settings are obtained to set the relay located at circuit breaker 1(CB1).
Protection functions
1MRS759142 F
1042
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......