Figure 336: Example of selection of setting Voltage start value in order to maximize
the earth-fault detection sensitivity of IFPTOC based on the resonance curve
calculated by the coil controller
To avoid unselective start or operation of IFPTOC,
Voltage start value
must always be set to a value which exceeds the maximum healthy-state
residual voltage value, taking into consideration of possible network
topology changes (variation in unbalance), compensation coil and parallel
resistor switching status (variation in damping) and compensation
degree variations (variation in detuning).
Activation of
EF_IND
output is determined to be the time instant when the
earth fault is detected. This information is needed as the IFPTOC utilizes “delta”
calculation i.e. changes in phase currents due to earth fault. For example, the
change of phase A current phasor due to earth fault can be written as:
(Equation 102)
Where:
t
FLT
is the time during the detected earth fault
t
PRE_FLT
is the time prior to detected earth fault occurrence and it represents
time during pre-fault or healthy-state conditions. This pre-fault operation point is
determined based on user setting
Revert time as follows:
(Equation 103)
1MRS759142 F
Protection functions
REX640
Technical Manual
587
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......