the circle is shifted to the right of the X-axis and if the sign is negative, the circle
is shifted to the left of the X-axis. For an origin-centric mho characteristic,
Offset
enable is kept disabled.
When using the mho-characteristics, the
Offset and Displacement
settings are as given in the UEXPDIS function, but
Polar reach is half of
UEXPDIS
Diameter setting.
X (Reactance) pu
R (Resistance) pu
Operating Region
Polar reach
Displacement
Offset
Figure 572: Designing zones with Offset and Displacement
The offset-mho characteristic shown in Figure
is designed with a positive
value for
Offset and a negative value for Displacement.
More than one impedance value is available when
Impedance Meas
mode is set to "3Phase-phase", and the function considers the lowest
impedance value for starting and operating.
Timer
Once activated, the Timer activates
START
output. The time characteristic is
according to DT. When the duration of the underimpedance condition exceeds the
set definite
Operate delay time, the
OPERATE
output is activated. If the impedance
locus moves out of circular operating characteristics before the module operates,
the reset timer is activated. If the reset timer reaches the value set by
Reset delay
time, the operating timer resets and the
START
output is deactivated.
The Timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operating time (DT). The value
is available in the Monitored data view.
Protection functions
1MRS759142 F
1030
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......