Figure 687: Fault loop impedance for a three-phase fault loop (“ABC Fault”)
The three-phase fault distance is calculated with a special measuring element
using positive-sequence quantities. This is advantageous especially in case of non-
transposed (asymmetric) lines, as the influence of line parameter asymmetry is
reduced. If the line is non-transposed, all the phase-to-phase loops have different
fault loop reactances. The use of positive-sequence quantities results in the average
value of phase-to-phase loop reactances, that is, the most representative estimate
in case of three-phase faults.
The fault distance calculation algorithm for the three-phase fault loop is defined
with settings
Load Com PP loops and Enable simple model. Options for the
selection are "Disabled" or "Enabled".
Load compensation can be enabled or disabled with setting
Load Com PP loops.
The load compensation should be disabled only if the ratio between the fault
current and load current is high or when the value of the fault distance estimate
for the short circuit fault is required from each shot of an autoreclosing sequence.
The fault distance calculation is most accurate when the calculation is made with
the fault loop model. This model requires positive sequence impedances of the
protected feeder to be given as settings. If these settings are not available, valid
impedance values can be calculated also without the fault loop model with setting
Enable simple model = "Enabled". However, a valid distance estimate, that is, the
conversion of measured impedance (“electrical fault distance’’) into a physical fault
distance requires accurate positive-sequence impedance settings.
Estimation of fault resistance in different fault loops
The fault point resistance value provided by the impedance calculation is available in
recorded data Flt point resistance and it depends on the applied fault loop as shown
. In case of earth faults, the estimated fault point resistance includes
the total fault point resistance between the faulty phase and earth, for example,
the arc and earthing resistances. In case of phase-to-phase faults, the estimated
fault point resistance is half of the total fault point resistance between the phases.
In case of a three-phase fault, the estimated fault point resistance equals the total
fault point resistance per phase, for example, the arc resistance per phase.
1MRS759142 F
Protection related functions
REX640
Technical Manual
1205
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......