
at the rated burden, the rated burden S
n
, the internal burden S
in
and the actual
burden S
a
of the CT.
F
F
S
S
S
S
a
n
in
n
in
a
=
⋅
+
+
(Equation 173)
Example 1
In the example, the rated burden S
n
of the CTs 5P20 is 10 VA, the secondary
rated current 5A, the internal resistance R
in
= 0.07 Ω and the accuracy limit
factor F
n
(ALF) corresponding to the rated burden is 20 (5P20). The internal
burden of the current transformer is S
in
= (5 A)
2
· 0.07 Ω = 1.75 VA. The
input impedance of the relay at a rated current of 5 A is < 20 mΩ. If the
measurement conductors have a resistance of 0.113 Ω, the actual burden of
the current transformer is S
a
=(5 A)2 · (0.113 + 0.020) Ω = 3.33 VA. Thus the
accuracy limit factor F
a
corresponding to the actual burden is 46.
The CT burden can grow considerably at the rated current of 5 A. At the
rated current of 1 A, the actual burden of the current transformer decreases,
while the repeatability simultaneously improves.
At faults occurring in the protected area, the fault currents can be very high
compared to the rated currents of the CTs. Due to the instantaneous stage
of the differential function block, it is enough that during the first cycle, the
CTs can repeat the current required for instantaneous tripping.
The CTs should be able to reproduce the asymmetric fault current without
saturating within the next 10 ms after the occurrence of the fault, to secure
that the operating times of the protection relay comply with the times
stated in
Chapter 4.3.3.12 Technical data
.
The accuracy limit factors corresponding to the actual burden of the
phase current transformer to be used in differential protection fulfill the
requirement of the equation.
Fa > K I
(T
(1 - e
) + 1)
r
kmax
dc
-
Tm
⋅
⋅
⋅
ω
Tdc
(Equation 174)
I
kmax
Maximum through-going fault current (in pu) at which the protection is not
allowed to operate
T
dc
Primary DC time constant related to I
kmax
ω
Angular frequency, that is, 2 · π · 50 Hz
T
m
Time to saturate, that is, the duration of the saturation-free transformation
K
r
Remanence factor, 1/(1-r)
The parameter
r gives the maximum remanence flux density in the CT core.
The value of the parameter
r depends on the magnetic material used and on
the construction of the CT. For example, the value
r = "0.4" means that the
remanence flux density may be 40 percent of the saturation flux density. The
manufacturer of the CT should be contacted when an accurate value for the
parameter
r is needed. The value r = "0.4" is recommended to be used when
an accurate value is not available.
Protection functions
1MRS759142 F
740
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......