
(Equation 104)
Maximum fault current value is obtained when fault resistance (
R
F
) is zero, in case of
can be written as:
(Equation 105)
Interpretation of
is that fault current has resistive part due to network
damping and imaginary part due to network detuning. Fault current magnitude
increases when damping or detuning increases.
The effect of fault resistance to fault current magnitude can be written as:
(Equation 106)
where
(Equation 107)
Interpretation of
is that effect of fault resistance to fault current
magnitude is proportional to scaling the fault current magnitude at zero fault
resistance with the per unit value of residual voltage (
) due to fault resistance.
Minimum fault current magnitude is always obtained at resonance, when detuning
(
I
v
) is zero, in case
can be written as:
(Equation 108)
At resonance, fault current is only due to system resistive shunt losses i.e. due to
network damping (
I
d
) and possible harmonic components.
In case of unearthed network, detuning value (
I
v
) equals the uncompensated earth-
fault current due to total network phase-to-earth capacitance value. In case of high
resistance earthed network detuning value (
I
v
) equals the uncompensated earth-
1MRS759142 F
Protection functions
REX640
Technical Manual
589
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......