sensor setting
Primary current. Taken from the sensor’s technical data, this
example sensor can be used with up to 4000 A application nominal current.
As the Rogowski sensor is linear and does not saturate, the 80 A/0.150 V at
50 Hz sensor also works as a 150 A/0.28125 V at 50 Hz sensor. When defining
another primary value for the sensor, also the nominal voltage has to be
redefined to maintain the same transformation ratio. However, the setting
in the protection relay (
Rated Secondary Value) is not in V but in mV/Hz,
which makes the same setting
Rated Secondary Value valid for both 50 and
60 Hz nominal frequency.
RSV
I
I
K
f
n
pr
r
n
=
×
(Equation 1)
RSV
Rated Secondary Value
in mV/Hz
I
n
Application nominal current
I
pr
Sensor-rated primary current
f
n
Network nominal frequency
K
r
Sensor-rated voltage at the rated current in mV
In this example, the value is as calculated using the equation.
150
80
150
50
5 625
A
A
mV
Hz
mV
Hz
×
=
.
(Equation 2)
With this information, the protection relay's current (Rogowski) sensor
settings can be set.
Table 92: Example setting values for current (Rogowski) sensor
Setting
Value
Primary current
150 A
Rated secondary value
5.625 mV/Hz
When considering setting values for current sensor interfaces and for
protection functions utilizing these measurements, it should be noted
that the sensor measurement inputs in the relay have limits for linear
behavior. When this limit is exceeded, the input starts to saturate. The
saturation is reflected to the protection functions connected to the
sensor inputs. To ensure that the related protection functions operate
correctly, the start value setting for protection functions utilizing either
instantaneous or definite minimum time characteristics must not exceed
the linear measurement range. Furthermore, the effect on protection
functions utilizing inverse time characteristics should be considered. The
upper limit of the linear measurement range depends on the selected
application nominal current and the type of the current sensor used.
shows the limits for an 80A/150mV 50Hz sensor.
Basic functions
1MRS759142 F
158
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......